Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 12, 2017, 06:37 AM
Date
10/11/2017
W/O
663065
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00601
PipeID
P12545
Time
11:37 PM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4828
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_663065_TV15183_OCT2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0610
Downstream MH
B 0788
Dir. of Survey
Upstream
Length Surveyed
20 ft.
Total Length
20 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 15 0610 to B 0788
MH: 15 0610MH: B 0788upstream0 ft. AMH - Upstream Manhole, Survey Ends - B 078812.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES20 ft. AMH - Downstream Manhole, Survey Begins - 15 061020 ft. MWL - Water Level, 5 %of cross sectional area20 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    7.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (5)

DistanceCodeObservation
0AMH15 0610
20AMHB 0788
7.6FM
0MWL
0MWM

Properties (4)

additional_info
SC353079
custom_field_two
3
customer
LACSD
datetime
2017-10-11T23:37:19-07:00