- Date
- 12/07/2017
- W/O
- 0630217
- Weather
- Dry
- Operator/Surveyor
- FRANKLIN
- Sewer ID
- Z00177
- PipeID
- P10845
- Time
- 8:53 AM
- Certificate
- U-415-06024039
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7576
- Sewer Name
- H JOINT OUTFALL H - UNIT 5A
- City
- WHITTIER
- Loc. details
- Other
- Location Code
- Z
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 33
- Purpose
- Capital Improvement Program Assesment
- Project
- 20171207DF_JOINT_OUTFALL_H_UNIT_5A
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 57 in.
- Upstream MH
- H 0411
- Downstream MH
- H 0410
- Dir. of Survey
- Downstream
- Length Surveyed
- 414 ft.
- Total Length
- 414 ft.
- Structural Index
- 3
- Structural Quick
- 3121
- Structural Rating
- 5
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole H 0411 to H 0410 Observation photos (6)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 30% mag coat

79 ft. - General Photograph

251 ft. - General Photograph - AGGREGATE

352 ft. - General Photograph