Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2017, 10:27 AM
  • C 0396_C 0395 _11282017_022821.mp4

Date
11/28/2017
W/O
674250
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00143
PipeID
P09864
Time
2:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5231
Sewer Name
C JOINT OUTFALL C - UNIT 8E
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
WO_674250_TV02139_DEC2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
C 0396
Downstream MH
C 0395
Dir. of Survey
Downstream
Length Surveyed
402.8 ft.
Total Length
402.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
412\
O&M Rating
296
Overall Index
2
Overall Quick
Overall Rating
296
Pipe schematic from manhole C 0396 to C 0395
MH: C 0396MH: C 0395downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03960 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start10.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start113.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"131.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"401.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish401.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish402.8 ft. AMH - Downstream Manhole, Survey Ends - C 0395

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    72.3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0AMHC 0396
2DAGS
0MWM
401.2DAE
402.8AMHC 0395
72.3DAE
401.2DAGS
131.1TBA
0MWL
113.2TBA
312.7TBA
10.1TBA

Properties (5)

additional_info
SC346402
custom_field_two
4
customer
LACSD
datetime
2017-11-28T02:27:45-08:00
year_laid
26597