Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 22, 2017, 08:18 AM
  • H 1485_H 1484 _22112017_001940.mp4

Date
11/22/2017
W/O
668874
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01206
PipeID
P16445
Time
12:18 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5044
Sewer Name
H JOINT OUTFALL H - UNIT 8M RELIEF
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_668874_TV22148_NOV2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
H 1485
Downstream MH
H 1484
Dir. of Survey
Downstream
Length Surveyed
758.2 ft.
Total Length
758.2 ft.
Structural Index
4
Structural Quick
5]3]
Structural Rating
1208
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
1208
Pipe schematic from manhole H 1485 to H 1484
MH: H 1485MH: H 1484downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14852.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start758.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish758.2 ft. AMH - Downstream Manhole, Survey Ends - H 1484758.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2.1SRV
0MWL
758.2SRV
758.2AMHH 1484
0MWM
0AMHH 1485
758.2SAP
2.1SAP

Properties (4)

additional_info
SC346273
custom_field_two
2
customer
LACSD
datetime
2017-11-22T00:18:35-08:00