Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2017, 08:40 AM
  • 05 1147_05 1146 _11072017_004059.mp4

Date
11/07/2017
W/O
668648
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00436
PipeID
P06386
Time
12:40 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5211
Sewer Name
05 EAST ROSECRANS AVENUE TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_668648_TV05270_NOV2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1147
Downstream MH
05 1146
Dir. of Survey
Downstream
Length Surveyed
337.6 ft.
Total Length
337.6 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
201
O&M Index
3
O&M Quick
3L2L
O&M Rating
332
Overall Index
3
Overall Quick
Overall Rating
533
Pipe schematic from manhole 05 1147 to 05 1146
MH: 05 1147MH: 05 1146downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 11470 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start6.2 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS66.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"318 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"335.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish335.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE335.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish335.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish337.6 ft. MGO - General Observation - CAPPED CONNECTIONS AT MH 3 AND 9 O'CLOCK337.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1146

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start - DEBRIS

    6.2 ft. - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS

Observations (19)

DistanceCodeObservation
6.2DSZDEBRIS
335.9DAGS
337.6MGOCAPPED CONNECTIONS AT MH 3 AND 9 O'CLOCK
66.6TFA
0MGOCOCKROACHES IN MANHOLE
0MWL
117.7TFC
335.9MGOCOCKROACHES IN MANHOLE
184.3TFC
0AMH05 1147
318TFA
337.6AMH05 1146
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
257.6TFC
335.9SAP
2SAP
2DAGS
335.9DSZ
0MWM

Properties (4)

additional_info
SC346082
custom_field_two
4
customer
LACSD
datetime
2017-11-07T00:40:40-08:00