Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 24, 2015, 03:36 PM
  • 15 0658_15 0657_20151211_121451.mp4

Date
10/24/2015
W/O
531423
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00606
PipeID
P12930
Time
8:36 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2287
Sewer Name
15 GRAND AVENUE TRUNK
City
SAN GABRIEL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
10
Purpose
Routine Assessment
Project
WO_531423_TV15027_OCT2015
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0658
Downstream MH
15 0657
Dir. of Survey
Downstream
Length Surveyed
306.7 ft.
Total Length
306.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0658 to 15 0657
MH: 15 0658MH: 15 0657downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01120 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area7 ft. MGO - General Observation - MAG COAT 45%7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start10.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start25.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"70.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"76.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"82.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"100 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"148 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"175.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"189.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"242 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"287.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"297.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"304.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish304.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish306.7 ft. AMH - Downstream Manhole, Survey Ends - 0127306.7 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK ACTIVE

Observation photos (1)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
304.3DAGS
76.1TFA
148TFC
287.3TFC
175.8TFA
7MGOMAG COAT 45%
306.7AMH0127
100TFA
25.7TFA
10.6SAV
0AMH0112
304.3SAV
82.8TFA
242TFA
306.7MGOCONNECTION AT MH 9 OCLOCK ACTIVE
0MWM
70.7TFA
297.7TFA
7DAGS
189.8TFA
0MWL

Properties (4)

additional_info
SC205369
custom_field_two
3
customer
LACSD
datetime
2015-10-24T08:36:15-07:00