Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2017, 09:27 AM
  • Section#1_J 0226_J 0225__12162017__G6884.mp4

Date
12/16/2017
W/O
0624519
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11472
Time
1:27 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6884
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20171216MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0226
Downstream MH
J 0225
Dir. of Survey
Downstream
Length Surveyed
425.7 ft.
Total Length
425.7 ft.
Structural Index
3
Structural Quick
5B4F
Structural Rating
484
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
484
Pipe schematic from manhole J 0226 to J 0225
MH: J 0226MH: J 0225downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:45AM2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR8 ft. SRV - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - LONG REBAR8.3 ft. MGO - General Observation - 27" RCP17.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR29.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR31.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR63.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Finish - LONG & CIRCUM REBAR77 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG109.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE162.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG162.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORATIC317.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE425 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC425 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE425 ft. MGO - General Observation - MH CONN 9:00 STUB425 ft. MGO - General Observation - MH CONN 3:00 STUB425.7 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (11)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - LONG REBAR

    8 ft. - Surface Reinforcement Visible, from 02 to 03 o'clock, within 8 inches of joint: NO - LONG REBAR

  • General Observation - 27" RCP

    8.3 ft. - General Observation - 27" RCP

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR

    29.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: NO, Start - LONG & CIRCUM REBAR

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    31.2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    77 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    109.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORATIC

    162.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORATIC

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    317.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

Observations (22)

DistanceCodeObservation
2SRCLONG & CIRCUM REBAR
0MWM
29.2SRVLONG & CIRCUM REBAR
0MWL
425.7AMH2:30AM
17.7SRCLONG & CIRCUM REBAR
317.1SSSPEELING CONCRETE
425SAVSEVERE AGG SPORATIC
425SSSBLISTERING PEELING CONCRETE
77SAMSEVERE AGG
2SAMSEVERE AGG
8SRCCIRCUM REBAR
8SRVLONG REBAR
162.2SAMSEVERE AGG
0AMH1:45AM
162.2SAVSPORATIC
425MGOMH CONN 9:00 STUB
109.3SSSBLISTERING PEELING CONCRETE
31.2SRVCIRCUM REBAR
63.1SRVLONG & CIRCUM REBAR
8.3MGO27" RCP
425MGOMH CONN 3:00 STUB

Properties (5)

custom_field_three
LONG & CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2017-12-16T01:27:53-08:00
year_laid
20020501