Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2015, 07:34 AM
Date
10/30/2015
W/O
521098
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00238
PipeID
P03822
Time
12:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2819
Sewer Name
02 BELVEDERE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_521098_TV02329_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1303
Downstream MH
02 1302
Dir. of Survey
Downstream
Length Surveyed
321.1 ft.
Total Length
321.1 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
123
O&M Index
2
O&M Quick
2V16
O&M Rating
236
Overall Index
2
Overall Quick
Overall Rating
359
Pipe schematic from manhole 02 1303 to 02 1302
MH: 02 1303MH: 02 1302downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 13030 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start44.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"58.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start85.1 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR91.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"95.6 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Start113.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start119.7 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR, Finish144 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"194 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"242.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"246.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"250.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"292.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"319.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish319.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish319.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish321.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK321.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE321.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1302

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    113.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
319.2CM
246.6TBA
0MWM
242.1TFC
319.2DAGS
292.3TFC
44.4TFA
113.4CM
144TFA
321.1MGOACTIVE CONNECTION AT MH 3 O'CLOCK
119.7RFJ
321.1MGOCOCKROACHES IN MANHOLE
58.5DAE
95.6RFJ
2DAGS
194TFA
319.2DAE
91.8TFA
0AMH02 1303
85.1RFJ
250.1TBA
321.1AMH02 1302
0MWL

Properties (4)

additional_info
SC204151
custom_field_two
3
customer
LACSD
datetime
2015-10-30T00:34:47-07:00