Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2015, 06:59 AM
  • E 0114_E 0113_07122015_230205.mp4

Date
12/07/2015
W/O
520989
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00032
PipeID
P11340
Time
10:59 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2841
Sewer Name
E JOINT OUTFALL E - UNIT 5
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_520989_TV01102_SEPT2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
E 0114
Downstream MH
E 0113
Dir. of Survey
Downstream
Length Surveyed
585.9 ft.
Total Length
585.9 ft.
Structural Index
3
Structural Quick
3V00
Structural Rating
348
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
348
Pipe schematic from manhole E 0114 to E 0113
MH: E 0114MH: E 0113downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 01140 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 60%584.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish585.9 ft. AMH - Downstream Manhole, Survey Ends - E 0113

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
2SAV
585.9AMHE 0113
0MWL
0AMHE 0114
2MGOMAG COATING 60%
584.5SAV
0MWM

Properties (6)

additional_info
SC204176
custom_field_two
3
customer
LACSD
datetime
2015-12-07T22:59:19-08:00
sewer_category
GRAVITY
year_laid
19870402