Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 12, 2015, 10:40 AM
  • 18 0808_18 0807_20151112_025201.mp4

Date
11/12/2015
W/O
531105
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00706
PipeID
P14669
Time
2:40 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2860
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
14
Purpose
Routine Assessment
Project
WO_531105_TV18114_OCT2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
18 0807
Downstream MH
18 0808
Dir. of Survey
Upstream
Length Surveyed
167.6 ft.
Total Length
167.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 18 0807 to 18 0808
MH: 18 0807MH: 18 0808upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 0808 (0251)3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish165.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start167.6 ft. AMH - Downstream Manhole, Survey Begins - 18 0807 (0240)167.6 ft. MWL - Water Level, 10 %of cross sectional area167.6 ft. MGO - General Observation - LATERAL AT MH 3 0CLOCK167.6 ft. MWM - Water Mark, 20 %of cross sectional area

Observations (7)

DistanceCodeObservation
164.6DAGS
0AMH18 0807 (0240)
0MWL
0MGOLATERAL AT MH 3 0CLOCK
167.6AMH18 0808 (0251)
0MWM
2DAGS

Properties (5)

additional_info
SC205625
custom_field_two
4
customer
LACSD
datetime
2015-11-12T02:40:12-08:00
sewer_category
GRAVITY