Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2015, 08:56 AM
  • 18 0240_18 0239_20151110_011652.mp4

Date
11/10/2015
W/O
531089
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00674
PipeID
P14068
Time
12:56 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2858
Sewer Name
18 EAST IMPERIAL HIGHWAY TRUNK
City
SANTA FE SPRINGS, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_531089_TV18005_OCT2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
18 0239
Downstream MH
18 0240
Dir. of Survey
Upstream
Length Surveyed
379.5 ft.
Total Length
379.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0239 to 18 0240
MH: 18 0239MH: 18 0240upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 0240 (0116)3.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish3.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish31.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"82.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"121.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"191.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"246.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"297.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"348.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"369.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start374.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start379.5 ft. MWL - Water Level, 5 %of cross sectional area379.5 ft. AMH - Downstream Manhole, Survey Begins - 18 0239 (0056)379.5 ft. MWM - Water Mark, 35 %of cross sectional area379.5 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK379.5 ft. MGO - General Observation - LATERAL AT MH 3 0CLOCK

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
379.5AMH18 0240 (0116)
10.4CM
81.7TFA
31.2TFC
133.1TFA
297.1TFC
376.3DAGS
0MWL
4.7DAGS
0AMH18 0239 (0056)
0MWM
0MGOLATERAL AT MH 9 OCLOCK
347.8TFA
0MGOLATERAL AT MH 3 0CLOCK
187.9TFA
257.9TF
376.3CM

Properties (5)

additional_info
SC205624
custom_field_two
3
customer
LACSD
datetime
2015-11-10T00:56:00-08:00
sewer_category
GRAVITY