Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2015, 09:32 AM
  • 18 0241_18 0240_20151110_020027.mp4

Date
11/10/2015
W/O
531089
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00674
PipeID
P14069
Time
1:32 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2858
Sewer Name
18 EAST IMPERIAL HIGHWAY TRUNK
City
SANTA FE SPRINGS, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_531089_TV18005_OCT2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
18 0240
Downstream MH
18 0241
Dir. of Survey
Upstream
Length Surveyed
392.2 ft.
Total Length
392.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0240 to 18 0241
MH: 18 0240MH: 18 0241upstream0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 18 0241 (0159)1.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish68.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"119.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"169.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"214.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"220.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"267.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"317.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"368.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start373.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"388.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start392.2 ft. MWM - Water Mark, 20 %of cross sectional area392.2 ft. AMH - Downstream Manhole, Survey Begins - 18 0240 (0133)392.2 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    23.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
323.8TFC
392.2MGOLATERAL AT MH 9 OCLOCK
3.5DAGS
177.3TBA
392.2AMH18 0241 (0159)
0MWM
390.3CM
0AMH18 0240 (0133)
0MWL
272.9TFA
19TFC
74.3TFA
171.5TFC
124.5TFA
23.5CM
222.6TFC
390.3DAGS

Properties (5)

additional_info
SC205624
custom_field_two
3
customer
LACSD
datetime
2015-11-10T01:32:55-08:00
sewer_category
GRAVITY