Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 10, 2015, 10:25 AM
  • 18 0242_18 0241_20151110_024259.mp4

Date
11/10/2015
W/O
531089
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00674
PipeID
P14070
Time
2:25 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2858
Sewer Name
18 EAST IMPERIAL HIGHWAY TRUNK
City
SANTA FE SPRINGS, CA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
WO_531089_TV18005_OCT2015
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
18 0242
Downstream MH
18 0241
Dir. of Survey
Downstream
Length Surveyed
453.1 ft.
Total Length
453.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 18 0242 to 18 0241
MH: 18 0242MH: 18 0241downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 0242 (0226)0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start65.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"168.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"270.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"411.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"445.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish450.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish453.1 ft. AMH - Downstream Manhole, Survey Ends - 18 0242 (0242)453.1 ft. MGO - General Observation - LATERAL AT MH 3 0CLOCK

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
453.1AMH18 0242 (0242)
2.1DAGS
0AMH18 0242 (0226)
270.6TFA
168.1TF
7.4CM
0MWM
411.1TFC
0MWL
453.1MGOLATERAL AT MH 3 0CLOCK
450.9DAGS
65.8TFC
445.2CM

Properties (5)

additional_info
SC205624
custom_field_two
3
customer
LACSD
datetime
2015-11-10T02:25:32-08:00
sewer_category
GRAVITY