Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 21, 2017, 11:41 AM
  • 14 0485_14 0484 _11212017_041438.mp4

Date
11/21/2017
W/O
674154
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00573
PipeID
P18574
Time
3:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5224
Sewer Name
14 FERN AVENUE TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
WO_674154_TV14010_DEC2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
14 0485
Downstream MH
14 0484
Dir. of Survey
Downstream
Length Surveyed
338.2 ft.
Total Length
338.2 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
322
Pipe schematic from manhole 14 0485 to 14 0484
MH: 14 0485MH: 14 0484downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 04850 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area5.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS28.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"30.9 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"79.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"81.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"129.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"132.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"180.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"183.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"230.3 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"233.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"281.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"284.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"336.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish338.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0484338.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
180.3TFC
30.9TF
336.9CM
281.5TFC
338.2AMH14 0484
183.3TFC
0AMH14 0485
129.8TFA
336.9DSZ
230.3TFC
28.5TFC
0MWL
81.9TFC
233.2TFC
284.3TFC
338.2MGOCOCKROACHES IN MANHOLE
79.2TFC
0MWM
132.8TFC
25DSZDEBRIS
5.9CM

Properties (5)

additional_info
SC346095
custom_field_two
3
customer
LACSD
datetime
2017-11-21T03:41:14-08:00
sewer_category
Gravity