Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2017, 07:47 AM
  • 05 2413_05 1369 _141117_000307.mp4

Date
11/13/2017
W/O
668745
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00444
PipeID
P06588
Time
11:47 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5217
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_668745_TV05295_NOV2017
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1369
Downstream MH
05 2413
Dir. of Survey
Upstream
Length Surveyed
298.9 ft.
Total Length
298.9 ft.
Structural Index
3
Structural Quick
5137
Structural Rating
26
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
26
Pipe schematic from manhole 05 1369 to 05 2413
MH: 05 1369MH: 05 2413upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 24133.4 ft. BVV - Broken Void Visible, from 12 to 04 o'clock, within 8 inches of joint: YES - BROKEN PIPE WITH A REPAIR BUT THERE IS A SMALL VOID AT THE VERY BOTTOM OF THE BREAK3.5 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES10.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES13.4 ft. MMC - Material Change, Vitrified clay pipe13.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish13.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish28.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start45.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"96.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"111 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish146.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"198 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"249.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"293.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start296.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start298.9 ft. AMH - Downstream Manhole, Survey Begins - 05 1369298.9 ft. MWM - Water Mark, 20 %of cross sectional area298.9 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (7)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    270.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Vitrified clay pipe

    285.5 ft. - Material Change, Vitrified clay pipe

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    288.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    295.4 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Broken Void Visible, from 12 to 04 o'clock, within 8 inches of joint: YES - BROKEN PIPE WITH A REPAIR BUT THERE IS A SMALL VOID AT THE VERY BOTTOM OF THE BREAK

    295.5 ft. - Broken Void Visible, from 12 to 04 o'clock, within 8 inches of joint: YES - BROKEN PIPE WITH A REPAIR BUT THERE IS A SMALL VOID AT THE VERY BOTTOM OF THE BREAK

Observations (19)

DistanceCodeObservation
187.9FL
152.3TFA
100.9TFC
270.1FL
253.2TFC
0AMH05 1369
49.1TFA
288.2CM
285.5MMC
298.9AMH05 2413
5FL
285.5FL
0MWM
295.5BVVBROKEN PIPE WITH A REPAIR BUT THERE IS A SMALL VOID AT THE VERY BOTTOM OF THE BREAK
285.5SAP
2SAP
202.2TFC
0MWL
295.4CM

Properties (5)

additional_info
SC346088
custom_field_two
2
customer
LACSD
datetime
2017-11-13T23:47:59-08:00
sewer_category
Gravity