Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2017, 06:48 AM
  • 05 1368_05 1422 _131117_231106.mp4

Date
11/13/2017
W/O
668745
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00444
PipeID
P06586
Time
10:48 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5217
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_668745_TV05295_NOV2017
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1368
Downstream MH
05 1422
Dir. of Survey
Downstream
Length Surveyed
301.6 ft.
Total Length
301.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
177
Pipe schematic from manhole 05 1368 to 05 1422
MH: 05 1368MH: 05 1422downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13680 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"82 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"83.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"130.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"180.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"231.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"282.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"298.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish298.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE301.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1422301.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK301.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLCOK

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
0MWL
130.8TFA
301.6AMH05 1422
180.9TFA
83.1TFC
82TBA
0AMH05 1368
282.8TFC
2SAP
0MWM
231.8TF
301.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK
298.6SAP
6.5TFA
298.6MGOCOCKROACHES IN MANHOLE
301.6MGOACTIVE CONNECTION AT MH 9 O'CLCOK

Properties (5)

additional_info
SC346088
custom_field_two
3
customer
LACSD
datetime
2017-11-13T22:48:03-08:00
sewer_category
Gravity