Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2017, 06:07 AM
  • 05 1369_05 1368 _131117_224613.mp4

Date
11/13/2017
W/O
668745
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00444
PipeID
P06587
Time
10:07 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5217
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_668745_TV05295_NOV2017
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 1369
Downstream MH
05 1368
Dir. of Survey
Downstream
Length Surveyed
311.4 ft.
Total Length
311.4 ft.
Structural Index
3
Structural Quick
413Q
Structural Rating
270
O&M Index
2
O&M Quick
312J
O&M Rating
117
Overall Index
3
Overall Quick
Overall Rating
387
Pipe schematic from manhole 05 1369 to 05 1368
MH: 05 1369MH: 05 1368downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13692 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.5 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES16.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"16.2 ft. RML - Roots Medium Lateral, from 12 to 06 o'clock, 40 %, within 8 inches of joint: YES25.2 ft. RFB - Roots Fine Barrell, from 12 to 12 o'clock, within 8 inches of joint: YES, Start63 ft. RFB - Roots Fine Barrell, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish63.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"99 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES115.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"141.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES164.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"179.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES183.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start226.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"277.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"304.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"309.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE309.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish311.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1368

Observation photos (8)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    14.5 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    16.2 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Fine Barrell, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    25.2 ft. - Roots Fine Barrell, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    99 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    141.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    179.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    183.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
304.9TFC
0MWL
164.4TFA
0MWM
183.7FL
25.2RFB
226.9TFA
16.2TFA
309.1SAP
2SAP
16.2RML
309.1MGOCOCKROACHES IN MANHOLE
99CL
179.1FL
309.1FL
311.4AMH05 1368
141.3FL
63RFB
115.5TFC
63.5TFA
0AMH05 1369
14.5FM
277.2TFA

Properties (5)

additional_info
SC346088
custom_field_two
2
customer
LACSD
datetime
2017-11-13T22:07:23-08:00
sewer_category
Gravity