Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2017, 06:12 AM
  • 05 1133_05 1092_11062017_221242.mp4

Date
11/06/2017
W/O
668623
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00436
PipeID
P06369
Time
10:12 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5210
Sewer Name
05 EAST ROSECRANS AVENUE TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_668623_TV05022_NOV2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 1133
Downstream MH
05 1092
Dir. of Survey
Downstream
Length Surveyed
445.1 ft.
Total Length
445.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312b
O&M Rating
355
Overall Index
2
Overall Quick
Overall Rating
355
Pipe schematic from manhole 05 1133 to 05 1092
MH: 05 1133MH: 05 1092downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 11332 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start51.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"202.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"352.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"442.9 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES442.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish442.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish445.1 ft. AMH - Downstream Manhole, Survey Ends - 05 1092445.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 12 O'CLOCK445.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES

    442.9 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
442.9DAGS
445.1AMH05 1092
442.9DAE
2DAE
202.3TFA
51.7TFA
442.9DAGS
445.1MGOACTIVE CONNECTION AT MH 3 AND 12 O'CLOCK
352.4TFC
0MWM
445.1MGOCOCKROACHES IN MANHOLE
0MWL
0AMH05 1133
2DAGS

Properties (5)

additional_info
SC346080
custom_field_two
4
customer
LACSD
datetime
2017-11-06T22:12:20-08:00
sewer_category
Gravity