Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2017, 09:30 AM
  • 02 0111_02 0110 __02112017_023220.mp4

Date
11/02/2017
W/O
668604
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00237
PipeID
P02278
Time
2:30 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5165
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFRLOWER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_668604_TV02350_NOV2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0111
Downstream MH
02 0110
Dir. of Survey
Downstream
Length Surveyed
309.3 ft.
Total Length
309.3 ft.
Structural Index
4
Structural Quick
5145
Structural Rating
33
O&M Index
2
O&M Quick
2411
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
42
Pipe schematic from manhole 02 0111 to 02 0110
MH: 02 0111MH: 02 0110downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01112 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.2 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES10.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: NO19.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.3 ft. FM - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES50.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.5 ft. VC - Vermin Cockroach73.2 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES78.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.6 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES100.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN124.6 ft. B - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES125.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN151.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"201.7 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES201.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"278.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"308 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES309.2 ft. MGO - General Observation - CONNECTION AT 9 OC309.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish309.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0110

Observation photos (12)

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    2 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    4.2 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: NO

    10.2 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    19.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

    37.3 ft. - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    73.2 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    99.6 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

    100.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

  • Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

    124.6 ft. - Broken, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

    125.1 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    201.7 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (30)

DistanceCodeObservation
100.6TFDBROKEN
56.5VC
151.5TF
201.9TF
0MWM
228.3TF
0MWL
309.2MGOCONNECTION AT 9 OC
172.3TF
278.6TFC
2FM
201.7FM
309.2CM
50.7TF
4.2CM
37.3FM
78.6TF
0AMH02 0111
309.3AMH02 0110
248.9TF
308DSF
73.2FM
99.6FM
10.2CL
125.1TFDBROKEN
19.5CM
124.6B
225.7TF
309.2DAGS
2DAGS

Properties (4)

additional_info
SC350365
custom_field_two
2
customer
LACSD
datetime
2017-11-02T02:30:01-07:00