Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 17, 2017, 06:24 AM
  • H 0401A_H 0401_16102017_232452.mp4

Date
10/16/2017
W/O
646746
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00177
PipeID
P10831
Time
11:24 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5024
Sewer Name
H JOINT OUTFALL H - UNIT 5A
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_646746_TV15130_JUL2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Width
60 in.
Upstream MH
H 0401A
Downstream MH
H 0401
Dir. of Survey
Downstream
Length Surveyed
472.5 ft.
Total Length
472.5 ft.
Structural Index
4
Structural Quick
5R3Q
Structural Rating
741
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
745
Pipe schematic from manhole H 0401A to H 0401
MH: H 0401AMH: H 0401downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 0401A10.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start165 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES472.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish472.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish472.5 ft. AMH - Downstream Manhole, Survey Ends - H 0401

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.5 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
10.4SAP
0MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0MWM
11.5SRV
0AMHH 0401A
472.4SRV
165SRV
472.2SAP
472.5AMHH 0401

Properties (4)

additional_info
SC346184
custom_field_two
2
customer
LACSD
datetime
2017-10-16T23:24:18-07:00