Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2017, 07:40 AM
  • 05 1723_05 1722 _011117_235602.mpg

Date
11/02/2017
W/O
669082
Weather
Dry
Operator/Surveyor
E RUIZ
Sewer ID
Z00471
PipeID
P06950
Time
12:40 AM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
5122
Sewer Name
05 LOMITA TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
WO_669082_TV05198_NOV2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 1723
Downstream MH
05 1722
Dir. of Survey
Downstream
Length Surveyed
365.3 ft.
Total Length
365.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
4200
O&M Rating
8
Overall Index
4
Overall Quick
Overall Rating
11
Pipe schematic from manhole 05 1723 to 05 1722
MH: 05 1723MH: 05 1722downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 17230 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH19.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"28.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start132.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"282.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish285.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"346.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"365.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1722365.3 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH

Observation photos (1)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    28.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
282.6CM
0MWM
132.1TF
0AMH05 1723
0MWL
365.3AMH05 1722
285.6TFA
19.3TFA
346.3TFA
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
365.3MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
28.9CM

Properties (5)

additional_info
SC348330
custom_field_two
3
customer
LACSD
datetime
2017-11-02T00:40:01-07:00
sewer_category
Gravity