Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2016, 09:47 AM
  • 15 0251_15 0250_20160517_033014.mp4

Date
05/17/2016
W/O
568734
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00627
PipeID
P12173
Time
2:47 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3352
Sewer Name
15 SAN JOSE CREEK TRUNK
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_568734_TV15001_MAY2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
15 0250
Downstream MH
15 0251
Dir. of Survey
Upstream
Length Surveyed
359.9 ft.
Total Length
359.9 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
213
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
363
Pipe schematic from manhole 15 0250 to 15 0251
MH: 15 0250MH: 15 0251upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 15 02511.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish8.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"18.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"174 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"198.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"335.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"352.8 ft. MGO - General Observation - MAG COATING 40%356.4 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start357.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start359.9 ft. AMH - Downstream Manhole, Survey Begins - 15 0250359.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE359.9 ft. MWL - Water Level, 20 %of cross sectional area359.9 ft. MWM - Water Mark, 25 %of cross sectional area

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    359.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
359.9MGOCOCKROACHES IN MANHOLE
161.8TBC
24.7TBC
351.3TBA
358.3SAV
0AMH15 0250
2DAGS
7.1MGOMAG COATING 40%
0MGOCOCKROACHES IN MANHOLE
150.8TBA
359.9AMH15 0251
0MWL
0MWM
341.8TBC
185.9TBC
358.3DAGS
3.5SAV

Properties (5)

additional_info
SC305632
custom_field_two
4
customer
LACSD
datetime
2016-05-17T02:47:05-07:00
sewer_category
GRAVITY