Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2016, 09:20 PM
  • 15 0264_15 0263_20160518_144416.mp4

Date
05/18/2016
W/O
568734
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00627
PipeID
P12187
Time
2:20 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3035
Sewer Name
15 SAN JOSE CREEK TRUNK
City
LA PUENTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_568734_TV15001_MAY2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
15 0264
Downstream MH
15 0263
Dir. of Survey
Downstream
Length Surveyed
296.7 ft.
Total Length
296.7 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
312K
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
299
Pipe schematic from manhole 15 0264 to 15 0263
MH: 15 0264MH: 15 0263downstream0 ft. VC - Vermin Cockroach0 ft. AMH - Upstream Manhole, Survey Begins - 15 02640 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.2 ft. MGO - General Observation - MAGNESIUM H.O. START100.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"189.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"189.2 ft. OBN - Obstacles Construction Debris, 20 %of cross sectional area, from 04 to 08 o'clock - NOT VISIBLE285.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"295.6 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH296 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish296.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish296.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0263

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAGNESIUM H.O. START

    4.2 ft. - General Observation - MAGNESIUM H.O. START

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    285.7 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    296 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    296.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (15)

DistanceCodeObservation
189.2TFC
296.7AMH15 0263
4.2MGOMAGNESIUM H.O. START
295.6MGOMAGNEZIUM H.O. FINISH
100.6TFC
0VC
0AMH15 0264
296SAV
189.2OBNNOT VISIBLE
2.4DAGS
296.1DAGS
285.7TFA
0MWM
2.4SAV
0MWL

Properties (5)

additional_info
SC226643
custom_field_two
4
customer
LACSD
datetime
2016-05-18T14:20:23-07:00
sewer_category
GRAVITY