Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2017, 11:14 AM
  • 22 0504_22 0088 _30102017_041516.mp4

Date
10/30/2017
W/O
668654
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00809
PipeID
P16843
Time
4:14 AM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4832
Sewer Name
22 HOLLENBECK STREET TRUNK
City
COVINA, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
32
Purpose
Routine Assessment
Project
WO_668654_TV22036_NOV2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0504
Downstream MH
22 0088
Dir. of Survey
Downstream
Length Surveyed
250.4 ft.
Total Length
250.5 ft.
Structural Index
4
Structural Quick
4A36
Structural Rating
66
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
66
Pipe schematic from manhole 22 0504 to 22 0088
MH: 22 0504MH: 22 0088downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 05048 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES16.3 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES20.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES23.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 4"24.6 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES28.7 ft. CM - Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES55.4 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"56.1 ft. FM - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES80.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES84.9 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES88.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 4"97 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES113.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES117.8 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES125.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES127.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"128.4 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES154.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"164.1 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES178.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"191.6 ft. FM - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES199.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES224.9 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES228.6 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES250.5 ft. AMH - Downstream Manhole, Survey Ends - 22 0088

Observation photos (18)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    16.3 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    20.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    24.6 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES

    28.7 ft. - Crack Multiple, from 10 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    56.1 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    80.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    84.9 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    97 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    113.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    117.8 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    125.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    128.4 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    164.1 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

    191.6 ft. - Fracture Multiple, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    199.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    224.9 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    228.6 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
199.4FM
191.6FM
113.7FM
0MWL
164.1FM
97FM
8CM
125.9CM
154.9TF
84.9FM
20.6FM
80.9FL
128.4FM
0MWM
56.1FM
117.8FM
127.7TFC
0AMH22 0504
178.1TF
224.9FM
28.7CM
16.3CM
24.6CM
23.7TB
55.4TF
228.6FM
88.4TB
250.5AMH22 0088

Properties (5)

additional_info
SC353094
custom_field_two
2
customer
LACSD
datetime
2017-10-30T04:14:42-07:00
sewer_category