Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2017, 05:56 AM
  • 22 0756_22 0755 _31102017_225832.mp4

Date
10/31/2017
W/O
668640
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00821
PipeID
P17114
Time
10:56 PM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4834
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
LA VERNE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
WO_668640_TV22056_NOV2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0756
Downstream MH
22 0755
Dir. of Survey
Downstream
Length Surveyed
394.3 ft.
Total Length
394.3 ft.
Structural Index
3
Structural Quick
4A39
Structural Rating
69
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
69
Pipe schematic from manhole 22 0756 to 22 0755
MH: 22 0756MH: 22 0755downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 07560 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area134.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES150 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES190.8 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES211.2 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES216.7 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES226.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES229.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"235 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"242.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES257.8 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES275.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"278.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES280.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"288.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES304 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES324.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES330.1 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES332.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"335.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES337.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"340.3 ft. FM - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES356 ft. CM - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES371.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES376.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES378.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6"382 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES383.9 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"387.1 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES394.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK394.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0755

Observation photos (20)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    134.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    150 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    190.8 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    211.2 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    216.7 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    226.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    242.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    257.8 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    278.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    288.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    304 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    324.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    330.1 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    335.3 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    340.3 ft. - Fracture Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

    356 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    371.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    376.6 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    382 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    387.1 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

Observations (33)

DistanceCodeObservation
394.3MGOCONNECTION AT MH 9 O'CLOCK
378.7TF
394.3AMH22 0755
332.7TFC
371.3CM
150CM
383.9TFC
275.8TFC
226.8CM
211.2FM
242.5FM
376.6FL
280.8TFC
235TFC
304FL
382CL
0AMH22 0756
229.3TFC
190.8CM
340.3FM
134.1FM
288.9FM
356CM
337.6TFC
0MWM
335.3FL
0MWL
324.9FL
257.8FM
330.1FM
216.7FM
387.1FM
278.6FM

Properties (5)

additional_info
SC353096
custom_field_two
2
customer
LACSD
datetime
2017-10-31T22:56:50-07:00
sewer_category
Gravity