Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 31, 2017, 09:08 AM
  • 22 0762_22 0761 _31102017_020903.mp4

Date
10/31/2017
W/O
668640
Weather
Dry
Operator/Surveyor
K. ADAME
Sewer ID
Z00821
PipeID
P17120
Time
2:08 AM
Certificate
07009000
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4833
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
LA VERNE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Routine Assessment
Project
WO_668640_TV22056_NOV2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0761
Downstream MH
22 0762
Dir. of Survey
Upstream
Length Surveyed
335.9 ft.
Total Length
335.9 ft.
Structural Index
3
Structural Quick
4438
Structural Rating
48
O&M Index
2
O&M Quick
2J12
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
162
Pipe schematic from manhole 22 0761 to 22 0762
MH: 22 0761MH: 22 0762upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 07620 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK18.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES23.4 ft. CM - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES49.3 ft. CM - Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES69.8 ft. CM - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES85.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"87.6 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES88.5 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"89.8 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES106 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES115.9 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES125.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES137 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"139.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"146.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES151.6 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES183.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"185.6 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"187.3 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES192.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES198.2 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES234.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"236.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"269.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES280.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start285.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"287.6 ft. RFJ - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES288 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"289.8 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES314.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES326.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: YES, 6"328.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 6"335.9 ft. MWL - Water Level, 10 %of cross sectional area335.9 ft. MWM - Water Mark, 20 %of cross sectional area335.9 ft. AMH - Downstream Manhole, Survey Begins - 22 0761

Observation photos (19)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    21.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    46.1 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

    48.3 ft. - Roots Fine Joint, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start

    55.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    66.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

    137.7 ft. - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    143.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    148.6 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    184.3 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    189.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    210 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    220 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    229.9 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    246.1 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    248.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

    266.1 ft. - Crack Multiple, from 09 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES

    286.6 ft. - Crack Multiple, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

    312.5 ft. - Crack Multiple, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    317.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (37)

DistanceCodeObservation
143.3CM
55.2DAGS
99TFC
247.4TFC
101.5TFC
184.3CM
0MWL
48.3RFJ
137.7RFJ
335.9AMH22 0762
150.3TFC
7.1TFC
0MWM
198.9TFC
152.8TFC
50.4TFC
312.5CM
335.9DAGS
148.6CM
335.9MGOCONNECTION AT MH 3 O'CLOCK
47.9TFC
46.1FM
220CL
317.4CM
229.9FM
248.3CL
9.5TFC
0AMH22 0761
210CL
189.6CL
196.3TFC
246.1FM
66.2FM
286.6CM
250.1TFC
266.1CM
21.6CM

Properties (5)

additional_info
SC353095
custom_field_two
3
customer
LACSD
datetime
2017-10-31T02:08:10-07:00
sewer_category