Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2017, 09:39 AM
  • 16 0319_16 0318 _20102017_024004.mp4

Date
10/20/2017
W/O
663187
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13370
Time
2:39 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5033
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
21
Purpose
Routine Assessment
Project
WO_663187_TV16060_OCT2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0319
Downstream MH
16 0318
Dir. of Survey
Downstream
Length Surveyed
278 ft.
Total Length
278 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
1
O&M Quick
4118
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
177
Pipe schematic from manhole 16 0319 to 16 0318
MH: 16 0319MH: 16 0318downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03190 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area4.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES6.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"37.1 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES43.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"51.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"81.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.9 ft. H - Hole, at 02 o'clock, within 8 inches of joint: NO104.2 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES111.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.2 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start139.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"185.7 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES218.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"238.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.3 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES271.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish278 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED278 ft. AMH - Downstream Manhole, Survey Ends - 16 0318

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    37.1 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Hole, at 02 o'clock, within 8 inches of joint: NO

    81.9 ft. - Hole, at 02 o'clock, within 8 inches of joint: NO

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    104.2 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    119.2 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    238.6 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (26)

DistanceCodeObservation
160.7TF
119.2RFJ
267.3RFJ
111.8TF
139.6RFJ
271.9CM
104.2RFJ
51.7TF
264.1TFA
185.7RFJ
278MGOCONNECTION AT MH 9 O'CLOCK CAPPED
69.3TF
0AMH16 0319
13.5TF
81.9H
218.5TF
4.6CM
6.9CM
0MWM
238.6TBA
81.4TF
180.7TF
278AMH16 0318
37.1RFJ
0MWL
43.7TF

Properties (5)

additional_info
SC346196
custom_field_two
2
customer
LACSD
datetime
2017-10-20T02:39:41-07:00
sewer_category
Gravity