Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2017, 05:44 AM
  • 16 0376_16 0375 _19102017_222233.mp4

Date
10/19/2017
W/O
663187
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13427
Time
10:44 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5033
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
WO_663187_TV16060_OCT2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
16 0376
Downstream MH
16 0375
Dir. of Survey
Downstream
Length Surveyed
317.6 ft.
Total Length
317.7 ft.
Structural Index
3
Structural Quick
4F3E
Structural Rating
223
O&M Index
1
O&M Quick
1D00
O&M Rating
23
Overall Index
3
Overall Quick
Overall Rating
246
Pipe schematic from manhole 16 0376 to 16 0375
MH: 16 0376MH: 16 0375downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03760 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area3.6 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES5 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES10.7 ft. RFJ - Roots Fine Joint, from 07 to 08 o'clock, within 8 inches of joint: YES15.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES23.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.8 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES40.8 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES53.9 ft. FS - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES56.2 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES, Start88 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES109.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start152.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish157.4 ft. RFJ - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES, Finish209.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.5 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"317.7 ft. AMH - Downstream Manhole, Survey Ends - 16 0375317.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (10)

  • Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES

    3.6 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    5 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    15.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    23.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

    40.8 ft. - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    40.8 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

    53.9 ft. - Fracture Spiral, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES, Start

    56.2 ft. - Roots Fine Joint, at 05 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    88 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    152.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
109.3TF
40.8FC
15.1CL
0AMH16 0376
0MWM
303.6TB
3.6RFJ
53.9FS
317.7AMH16 0375
157.4RFJ
23.2CM
0MGOCONNECTION AT MH 9 O'CLOCK
88FL
317.7FM
5CM
10.7RFJ
209.8TFC
0MWL
152.4FM
40.8RFJ
152.4CM
227.5TS
56.2RFJ

Properties (5)

additional_info
SC346196
custom_field_two
3
customer
LACSD
datetime
2017-10-19T22:44:29-07:00
sewer_category