Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2017, 07:02 AM
  • 16 0347_16 0346 _20102017_000508.mp4

Date
10/20/2017
W/O
663187
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13398
Time
12:02 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5033
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
WO_663187_TV16060_OCT2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0346
Downstream MH
16 0347
Dir. of Survey
Upstream
Length Surveyed
301.9 ft.
Total Length
301.9 ft.
Structural Index
3
Structural Quick
493G
Structural Rating
162
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
162
Pipe schematic from manhole 16 0346 to 16 0347
MH: 16 0346MH: 16 0347upstream0 ft. AMH - Upstream Manhole, Survey Ends - 16 03470 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK5.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES5.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish9.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"138.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start203.3 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES209.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.4 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES239.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES261.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start298.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES301.9 ft. MWM - Water Mark, 15 %of cross sectional area301.9 ft. AMH - Downstream Manhole, Survey Begins - 16 0346301.9 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (7)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    62.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    80.5 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    98.6 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    101.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    296.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
234.3TFC
62.4CM
21.5TFC
98.6CM
296.1FM
0MWM
292TFC
296CM
0AMH16 0346
101.3CM
92.4TFC
4.3FM
3.2FM
80.5CM
40.1FM
301.9AMH16 0347
301.9MGOCONNECTION AT MH 9 O'CLOCK
0MWL
163.4TFC

Properties (5)

additional_info
SC346196
custom_field_two
3
customer
LACSD
datetime
2017-10-20T00:02:33-07:00
sewer_category
Gravity