Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2016, 11:02 AM
  • 18 0660_18 0659 _12022016_032319.mp4

Date
12/02/2016
W/O
602450
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00696
PipeID
P14509
Time
3:02 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3895
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
WO_602450_TV18081_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0660
Downstream MH
18 0659
Dir. of Survey
Downstream
Length Surveyed
344.5 ft.
Total Length
344.5 ft.
Structural Index
3
Structural Quick
3B23
Structural Rating
48
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
51
Pipe schematic from manhole 18 0660 to 18 0659
MH: 18 0660MH: 18 0659downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06600 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE2.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES46.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start56.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start56.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish67.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"74 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"74 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish170.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"175.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"218.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start269.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"269.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"307.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES341.5 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH341.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish344.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0659

Observation photos (6)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    27.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    46.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    56.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    218.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    307.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
341.5MGOMAGNEZIUM H.O. FINISH
0MWM
74TFC
275TFC
2.6DAGS
46.2CL
0MWL
74CM
269.7TFA
27.7CL
307.8CL
341.5DAGS
0AMH18 0660
0VC
56.2CM
344.5AMH18 0659
67.9TFC
218.6CM
175.2TFC
269.7CM
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
56.2CL
170.3TFC

Properties (5)

additional_info
SC305229
custom_field_two
3
customer
LACSD
datetime
2016-12-02T03:02:30-08:00
sewer_category
Gravity