Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2016, 08:23 AM
  • 18 0669_18 0668 _12022016_004310.mp4

Date
12/02/2016
W/O
602450
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00696
PipeID
P14518
Time
12:23 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3895
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
WO_602450_TV18081_NOV2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0669
Downstream MH
18 0668
Dir. of Survey
Downstream
Length Surveyed
351 ft.
Total Length
351 ft.
Structural Index
2
Structural Quick
492C
Structural Rating
82
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
220
Pipe schematic from manhole 18 0669 to 18 0668
MH: 18 0669MH: 18 0668downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06692.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAGNESIUM H.O. START27.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start42.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"87 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish98.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"101.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"186 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES, Start198.2 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES, Finish198.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"203.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"208 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start221.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish221.7 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start243.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish267.7 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start292.3 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish301.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"306.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"310.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start344.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish348.8 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH348.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351 ft. AMH - Downstream Manhole, Survey Ends - 18 0668

Observation photos (8)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    27.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

    42.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES, Start

    186 ft. - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    208 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    221.7 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    267.7 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    310.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
101.3TFA
2.5MGOMAGNESIUM H.O. START
98.6TFA
87CL
348.8MGOMAGNEZIUM H.O. FINISH
198.2CC
243.3FM
203.7TFC
208CL
42.8TBA
267.7FM
306.7TFC
348.8DAGS
27.8CL
221.7CL
0MWL
0MWM
0AMH18 0669
198.2TFC
344.4CL
2.4DAGS
351AMH18 0668
310.7CL
301.2TFC
186CC
221.7FM
292.3FM

Properties (5)

additional_info
SC305229
custom_field_two
2
customer
LACSD
datetime
2016-12-02T00:23:30-08:00
sewer_category