Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 18, 2017, 06:18 AM
  • 22 1079_22 1078 _17102017_231950.mp4

Date
10/17/2017
W/O
646476
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00812
PipeID
P17452
Time
11:18 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5026
Sewer Name
22 IRWINDALE TRUNK, SECTS 2,3,4,&5
City
IRWINDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
18
Purpose
Routine Assessment
Project
WO_646476_TV22042_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 1079
Downstream MH
22 1078
Dir. of Survey
Downstream
Length Surveyed
408 ft.
Total Length
408 ft.
Structural Index
3
Structural Quick
5142
Structural Rating
31
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole 22 1079 to 22 1078
MH: 22 1079MH: 22 1078downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 8 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 22 10790.1 ft. MWM - Water Mark, 25 %of cross sectional area5.3 ft. CM - Crack Multiple, from 02 to 09 o'clock, within 8 inches of joint: YES20.5 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES51.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES66.6 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES78.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"87.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start104.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"120 ft. FM - Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES141.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES152.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"155.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.2 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"229.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"296.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"304.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"315.8 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES324.9 ft. B - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES - AT CONNECTION324.9 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: NO, 6"338 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"358 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"371 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"383.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"399.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish407 ft. MGO - General Observation - Surface Spalling throughout the reach408 ft. AMH - Downstream Manhole, Survey Ends - 22 1078408 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (9)

  • Crack Multiple, from 02 to 09 o'clock, within 8 inches of joint: YES

    5.3 ft. - Crack Multiple, from 02 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    20.5 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    51.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    66.6 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    87.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

    120 ft. - Fracture Multiple, from 06 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    141.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    315.8 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Broken, from 08 to 12 o'clock, within 8 inches of joint: YES - AT CONNECTION

    324.9 ft. - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES - AT CONNECTION

Observations (35)

DistanceCodeObservation
232.4TF
0MWL
371TFC
81.3TF
229.8TFC
194.2TB
51.6CM
399.4CM
0MGOCONNECTION AT MH 3 O'CLOCK
315.8FM
87.7CM
338TBA
120FM
0MGOCONNECTION AT MH 9 O'CLOCK
152.8TFC
408AMH22 1078
408MGOCONNECTION AT MH 9 O'CLOCK
0.1MWM
0MGOCONNECTION AT MH 8 O'CLOCK
20.5CM
78.8TFC
66.6CM
358TFC
0AMH22 1079
324.9BAT CONNECTION
407MGOSurface Spalling throughout the reach
304.1TFC
383.6TFC
5.3CM
109TB
141.7FL
296.5TFC
324.9TB
104.5TFC
155.6TFC

Properties (5)

additional_info
SC346186
custom_field_two
2
customer
LACSD
datetime
2017-10-17T23:18:42-07:00
sewer_category
Gravity