- Date
- 12/02/2017
- W/O
- 0674067
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00152
- PipeID
- P21294
- Time
- 12:52 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6876
- Sewer Name
- D JOINT OUTFALL D - UNIT 2B
- City
- GARDENA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 24
- Purpose
- Capital Improvement Program Assesment
- Project
- 20171202MDM_JOINT_OUTFALL_D_UNIT_2B
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 57 in.
- Upstream MH
- D 0052
- Downstream MH
- D JOINT
- Dir. of Survey
- Downstream
- Length Surveyed
- 8.2 ft.
- Total Length
- 8.2 ft.
- Structural Index
- 5
- Structural Quick
- 5442
- Structural Rating
- 28
- O&M Index
- 5
- O&M Quick
- 5100
- O&M Rating
- 5
- Overall Index
- 5
- Overall Quick
- —
- Overall Rating
- 33
Pipe schematic from manhole D 0052 to D JOINT Observation photos (4)

2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

4 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

8 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR