Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2017, 08:33 AM
  • Section#3_B 0003_B 0002__1212017__G6874.mp2

Date
12/01/2017
W/O
0672781
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00072
PipeID
P08513
Time
12:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6874
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
16
Purpose
Capital Improvement Program Assesment
Project
20171201MDM_JOINT_OUTFALL_B_UNIT_1A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Upstream MH
B 0002
Downstream MH
B 0003
Dir. of Survey
Upstream
Length Surveyed
1005.5 ft.
Total Length
1005.5 ft.
Structural Index
4
Structural Quick
5h4g
Structural Rating
2427
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
2432
Pipe schematic from manhole B 0002 to B 0003
MH: B 0002MH: B 0003upstream0 ft. AMH - Upstream Manhole, Survey Ends( COMPLETED REVERSE INSPECTION ZOOM 1000') - 3:30AM(COMPLETED REVERSE INSPECTION ZOOM 1000')0.5 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDER MAG COAT0.5 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDER MAG COAT0.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR0.5 ft. MGO - General Observation - MAG COAT 100% FINISH0.6 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR5.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR805.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR(ZOOM 200')997.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE1003.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR1003.5 ft. SAM - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT1003.5 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT1005.5 ft. MGO - General Observation - MAG COAT 100% START 10:00 TO 2:001005.5 ft. AMH - Downstream Manhole, Survey Begins - 3:00AM1005.5 ft. MWL - Water Level, 80 %of cross sectional area1005.5 ft. MWM - Water Mark, 80 %of cross sectional area

Observation photos (7)

  • General Observation - MAG COAT 100% START 10:00 TO 2:00

    0 ft. - General Observation - MAG COAT 100% START 10:00 TO 2:00

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

    2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR

  • Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    2 ft. - Surface Aggregate Missing, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR(ZOOM 200')

    200 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR(ZOOM 200')

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

    1000 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

    1004.9 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - BROKEN MISSING REBAR

Observations (16)

DistanceCodeObservation
0MGOMAG COAT 100% START 10:00 TO 2:00
1005SAPSEVERE AGG UNDER MAG COAT
2SRCBROKEN MISSING REBAR
0AMH3:00AM
200SRCBROKEN MISSING REBAR(ZOOM 200')
2SAMSEVERE AGG UNDER MAG COAT
1005.5AMH3:30AM(COMPLETED REVERSE INSPECTION ZOOM 1000')
1004.9SRCBROKEN MISSING REBAR
1000SRCBROKEN MISSING REBAR
2SAPSEVERE AGG UNDER MAG COAT
0MWL
1005SAMSEVERE AGG UNDER MAG COAT
1005SRCBROKEN MISSING REBAR
8TFACTIVE
0MWM
1005MGOMAG COAT 100% FINISH

Properties (4)

custom_field_three
BROKEN MISSING REBAR HANGING IN FLOW
custom_field_two
1
customer
LACSD
datetime