Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2017, 07:50 AM
  • 03 0038_03 0037_03082017_010744.mp4

Date
08/03/2017
W/O
646910
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z00366
PipeID
P05058
Time
12:50 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4769
Sewer Name
03 LOS COYOTES DIAGONAL TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
13
Purpose
Routine Assessment
Project
WO_646534_TV03011_JUL2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
03 0038
Downstream MH
03 0037
Dir. of Survey
Downstream
Length Surveyed
326.9 ft.
Total Length
326.9 ft.
Structural Index
3
Structural Quick
513B
Structural Rating
52
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 03 0038 to 03 0037
MH: 03 0038MH: 03 0037downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 003810.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.3 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES124.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES165.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"194.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish202.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.6 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES235.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES238.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start246.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES248.1 ft. HSV - Hole Soil Visible, at 02 o'clock, within 8 inches of joint: NO - LATERAL MISSING248.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN303.9 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES306.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"326.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish326.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0037

Observation photos (9)

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    102.3 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    137.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    220.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    235.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    238.7 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    246.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Hole Soil Visible, at 02 o'clock, within 8 inches of joint: NO - LATERAL MISSING

    248.1 ft. - Hole Soil Visible, at 02 o'clock, within 8 inches of joint: NO - LATERAL MISSING

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

    248.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    303.9 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
137.6CM
102.3CM
0MWL
246.8CL
10.6TF
248.1HSVLATERAL MISSING
194.5CM
202.2TF
165.7TF
306.4TF
0MWM
0AMH03 0038
67.9TF
326.9DSZ
235.4CM
248.1TFDBROKEN
220.6CM
238.7DSZ
326.9AMH03 0037
303.9CM
124.4TF

Properties (5)

additional_info
SC345529
custom_field_two
1
customer
LACSD
datetime
2017-08-03T00:50:44-07:00
sewer_category
Gravity