Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2017, 03:49 PM
  • A 0034_A 0033_1222017_084205.mp4

Date
12/02/2017
W/O
0635655
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00334
PipeID
P08409
Time
7:49 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7568
Sewer Name
A JOINT OUTFALL A - UNIT 3C
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
09
Purpose
Capital Improvement Program Assesment
Project
20171202DF_JOA_UNIT_3C
Material
RCP-CTL
Shape
Square
Height
78 in.
Width
78 in.
Upstream MH
A 0034
Downstream MH
A 0033
Dir. of Survey
Downstream
Length Surveyed
67.2 ft.
Total Length
67.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole A 0034 to A 0033
MH: A 0034MH: A 0033downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:05 AM9.1 ft. SZC - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - 80 % MAG COAT22.8 ft. SRP - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start56.8 ft. SAV - Surface Aggregate Visible, from 03 to 09 o'clock, within 8 inches of joint: YES, Start61.6 ft. MGP - General Photograph61.6 ft. MGP - General Photograph65.2 ft. SZC - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 80 % MAG COAT65.2 ft. SAV - Surface Aggregate Visible, from 03 to 09 o'clock, within 8 inches of joint: YES, Finish65.2 ft. SRP - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish67.2 ft. MGO - General Observation - Grease Throughout The Reach (5%)67.2 ft. AMH - Downstream Manhole, Survey Ends - 9:01 AM

Observation photos (4)

  • Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - 80 % MAG COAT

    9.1 ft. - Surface Other Chemical, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - 80 % MAG COAT

  • Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    22.8 ft. - Surface Reinforcement Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    61.6 ft. - General Photograph

  • General Photograph

    61.6 ft. - General Photograph

Observations (13)

DistanceCodeObservation
67.2MGOGrease Throughout The Reach (5%)
0MWM
0MWL
61.6MGP
67.2AMH9:01 AM
61.6MGP
56.8SAV
22.8SRP
65.2SZC80 % MAG COAT
65.2SAV
65.2SRP
0AMH8:05 AM
9.1SZC80 % MAG COAT

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-12-02T07:49:43-08:00