Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 8, 2017, 06:18 AM
  • 01 1198_01 1155_09072017_232136.mp4

Date
09/07/2017
W/O
651727
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00226
PipeID
P02108
Time
11:18 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4725
Sewer Name
01 WILCOX AVENUE TRUNK, EXTENSION #1
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
11
Purpose
Routine Assessment
Project
WO_651727_TV01250_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
01 1198
Downstream MH
01 1155
Dir. of Survey
Downstream
Length Surveyed
88.5 ft.
Total Length
88.5 ft.
Structural Index
3
Structural Quick
3B21
Structural Rating
47
O&M Index
2
O&M Quick
2B00
O&M Rating
34
Overall Index
2
Overall Quick
Overall Rating
81
Pipe schematic from manhole 01 1198 to 01 1155
MH: 01 1198MH: 01 1155downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11980 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start15 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"71.9 ft. MMC - Material Change, Cast Iron - CIP74.7 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start74.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish87.7 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish87.7 ft. JSL - Joint Separated Large87.8 ft. MMC - Material Change, Vitrified clay pipe88.4 ft. MGO - General Observation - ACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK88.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish88.5 ft. AMH - Downstream Manhole, Survey Ends - 01 115588.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Material Change, Cast Iron - CIP

    71.9 ft. - Material Change, Cast Iron - CIP

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    74.7 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Joint Separated Large

    87.7 ft. - Joint Separated Large

  • Material Change, Vitrified clay pipe

    87.8 ft. - Material Change, Vitrified clay pipe

Observations (16)

DistanceCodeObservation
71.9MMCCIP
87.7SCP
0AMH01 1198
88.4MGOACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK
0MWM
88.5AMH01 1155
87.8MMC
88.4DAGS
15CM
37.8TFC
88.5MGOCOCKROACHES IN MANHOLE
2DAGS
87.7JSL
74.7SCP
74.7CM
0MWL

Properties (5)

additional_info
SC345733
custom_field_two
3
customer
LACSD
datetime
2017-09-07T23:18:04-07:00
sewer_category
Gravity