- Date
- 11/25/2017
- W/O
- 0674132
- Weather
- Dry
- Operator/Surveyor
- Reveles
- Sewer ID
- Z01090
- PipeID
- P24439
- Time
- 10:30 AM
- Certificate
- U-115-06022630
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0681
- Sewer Name
- 29 ALAMITOS PUMPING PLANT SEWER
- City
- Signal Hill
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 29
- Page No.
- 03
- Purpose
- Capital Improvement Program Assesment
- Project
- 11252017VMR_ALAMITOS_PUMPING_PLANT_SEWER
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Upstream MH
- 29 0402
- Downstream MH
- 29 0401
- Dir. of Survey
- Downstream
- Length Surveyed
- 326.8 ft.
- Total Length
- 326.8 ft.
- Structural Index
- 2
- Structural Quick
- 3329
- Structural Rating
- 40
- O&M Index
- 1
- O&M Quick
- 3121
- O&M Rating
- 10
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 50
Pipe schematic from manhole 29 0402 to 29 0401 Observation photos (6)

11.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

36.8 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

90.6 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR

98.4 ft. - Obstacles Other, 5 %of cross sectional area, at 03 o'clock - Debris

125.6 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YESR

149.1 ft. - Roots Medium Joint, at 03 o'clock, 5 %, within 8 inches of joint: YESR