Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 10, 2015, 07:30 AM
  • 16 0601_16 0600_20151210_002938.mp4

Date
12/09/2015
W/O
531059
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00664
PipeID
P13651
Time
11:30 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3006
Sewer Name
16 PASADENA EAST-WEST INTERCEPTOR TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
10
Purpose
Routine Assessment
Project
WO_531059_TV16030_OCT2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Upstream MH
16 0601
Downstream MH
16 0600
Dir. of Survey
Downstream
Length Surveyed
1182.1 ft.
Total Length
1182.1 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
1
O&M Quick
2214
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole 16 0601 to 16 0600
MH: 16 0601MH: 16 0600downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 06010 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE0 ft. VC - Vermin Cockroach2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNEZIUM H.O. START2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start84.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"219.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"320.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"523.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"616.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"763.3 ft. VC - Vermin Cockroach814.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"896.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"1064.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"1137.8 ft. VC - Vermin Cockroach1178.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1178.1 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH1178.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1182.1 ft. AMH - Downstream Manhole, Survey Ends - 16 06001182.1 ft. VC - Vermin Cockroach1182.1 ft. MGO - General Observation - AIR VENT AT MH

Observation photos (2)

  • General Observation - MAGNEZIUM H.O. START

    2.1 ft. - General Observation - MAGNEZIUM H.O. START

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
1182.1AMH16 0600
1178.1DAGS
763.3VC
1137.8VC
896.2TFA
523.3TFA
1182.1VC
0AMH16 0601
1178.1MGOMAGNEZIUM H.O. FINISH
1178.1SAV
320.6TFA
616.8TFA
0MWL
1064.7TFA
2.1DAGS
219.5TFA
84.2TFA
0MWM
0MGOLATERAL AT MH 9 OCLOCK ACTIVE
814.1TFA
2.1MGOMAGNEZIUM H.O. START
2.1SAV
0VC
1182.1MGOAIR VENT AT MH

Properties (5)

additional_info
SC205698
custom_field_two
3
customer
LACSD
datetime
2015-12-09T23:30:56-08:00
sewer_category
GRAVITY