Wastewater/Activity/PacpInspection/1.0Nov 21, 2017, 08:33 AM
18 0209_18 0208_11212017_010332.mp4
Date
11/21/2017
W/O
0674937
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00695
PipeID
P14034
Time
12:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
—
Pre-Cleaning
Not Known
Media Label
HO675
Sewer Name
18 ORR AND DAY ROAD TRUNK
City
SANTE FE SPRINGS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
13
Purpose
Maintenance Related
Project
20171121MDM_ORR_AND_ROAD_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
18 0209
Downstream MH
18 0208
Dir. of Survey
Downstream
Length Surveyed
21 ft.
Total Length
21 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4132
O&M Rating
12
Overall Index
3
Overall Quick
—
Overall Rating
12
Pipe schematic from manhole 18 0209 to 18 0208
Observation photos (2)
8 ft. - General Observation - 27" RCP
9.5 ft. - Deposits Settled Compacted, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - HARD MATERIAL UNDER FLOW LEFT SIDE OF PIPE