- Date
- 11/20/2017
- W/O
- 0672781
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00072
- PipeID
- P08519
- Time
- 2:24 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6871
- Sewer Name
- B JOINT OUTFALL B - UNIT 1A
- City
- CARSON
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 14
- Purpose
- Capital Improvement Program Assesment
- Project
- 20171118MDM_JOINT_OUTFALL_B_UNIT_1A
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 144 in.
- Upstream MH
- B 0009
- Downstream MH
- B 0008
- Dir. of Survey
- Downstream
- Length Surveyed
- 312.9 ft.
- Total Length
- 312.9 ft.
- Structural Index
- 5
- Structural Quick
- 5W4K
- Structural Rating
- 846
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 5
- Overall Quick
- —
- Overall Rating
- 850
Pipe schematic from manhole B 0009 to B 0008 Observation photos (6)

2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR UNDER MAG COAT

2 ft. - General Observation - MAG COAT 100% 9:00 TO 3:00 START

36.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO, Start - BROKEN MISSING REBAR

104.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

218.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING CIRCUM REBAR

250.3 ft. - Surface Aggregate Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG