Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2017, 09:50 AM
  • 05 0900_05 0899 _05102017_025104.mp4

Date
10/05/2017
W/O
663034
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00512
PipeID
P06130
Time
2:50 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4905
Sewer Name
05 RAYMOND AVENUE TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
WO_663034_TV05096_OCT2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0900
Downstream MH
05 0899
Dir. of Survey
Downstream
Length Surveyed
315.9 ft.
Total Length
315.9 ft.
Structural Index
3
Structural Quick
3622
Structural Rating
22
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 05 0900 to 05 0899
MH: 05 0900MH: 05 0899downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 09000 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK, ACTIVE0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area3.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES20.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES44.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"45 ft. MGO - General Observation - GASKET HANGING78.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES91.2 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES93.2 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES96 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES97.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.2 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start99.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6" - BROKEN198.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"200.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"246.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"302.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.2 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish314 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH315.9 ft. AMH - Downstream Manhole, Survey Ends - 05 0899315.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK, ACTIVE

Observation photos (7)

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    20.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    78.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    91.2 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    93.2 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    96 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    98.2 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
312.2CM
315.9AMH05 0899
91.2CM
96CL
200.5TF
3.1CL
0AMH05 0900
315.9MGOCONNECTION AT MH 3 O'CLOCK, ACTIVE
97.2TF
99.5TF
93.2CM
302.1TF
198.1TF
152.8TFDBROKEN
150.1TF
246.1TF
45MGOGASKET HANGING
98.2CM
0MGOCONNECTION AT MH 9 O'CLOCK, ACTIVE
314MGOSPALLING THROUGHOUT THE REACH
0MWL
248.8TF
44.2TF
20.5CM
0MWM
78.8CM

Properties (4)

additional_info
SC346165
custom_field_two
3
customer
LACSD
datetime
2017-10-05T02:50:17-07:00