Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2017, 08:28 AM
  • 08 0386_08 0385 _13092017_012840.mp4

Date
09/13/2017
W/O
651708
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00003
PipeID
P00438
Time
1:28 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4872
Sewer Name
08 DAVIDSON CITY TRUNK, SECTS 1,2,&3
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
12
Purpose
Routine Assessment
Project
WO_651708_TV08001_AUG2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
08 0385
Downstream MH
08 0386
Dir. of Survey
Upstream
Length Surveyed
417.7 ft.
Total Length
417.7 ft.
Structural Index
3
Structural Quick
423H
Structural Rating
148
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
148
Pipe schematic from manhole 08 0385 to 08 0386
MH: 08 0385MH: 08 0386upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 03869.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"28.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES96.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish105.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"121.9 ft. FM - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES121.9 ft. H - Hole, from 01 to 02 o'clock, within 8 inches of joint: YES207.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"305.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"314.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start366.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES386.3 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES396.9 ft. CC - Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES407.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"417.7 ft. MWM - Water Mark, 15 %of cross sectional area417.7 ft. AMH - Downstream Manhole, Survey Begins - 08 0385417.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (7)

  • Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

    20.8 ft. - Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    31.4 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    51.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    102.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    295.8 ft. - Fracture Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

  • Hole, from 01 to 02 o'clock, within 8 inches of joint: YES

    295.8 ft. - Hole, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    389.1 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
311.9TFC
389.1CL
10.1TFC
20.8CC
0MWM
51.4CL
321.4CM
0AMH08 0385
102.8CM
295.8FM
112.2TFC
295.8H
209.8TFC
0MWL
408.4TFC
417.7AMH08 0386
31.4CM

Properties (5)

additional_info
SC345931
custom_field_two
1
customer
LACSD
datetime
2017-09-13T01:28:15-07:00
sewer_category