Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 19, 2017, 09:05 AM
Date
09/19/2017
W/O
654216
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00839
PipeID
P19627
Time
2:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4879
Sewer Name
32 SAN FERNANDO ROAD TRUNK
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_630370_TV05315_AUG2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1173
Downstream MH
32 1172
Dir. of Survey
Downstream
Length Surveyed
495.9 ft.
Total Length
495.9 ft.
Structural Index
3
Structural Quick
3S2S
Structural Rating
493
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
494
Pipe schematic from manhole 32 1173 to 32 1172
MH: 32 1173MH: 32 1172downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 11730 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT93.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"97.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"332.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"397.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"418.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"418.3 ft. RFL - Roots Fine Lateral, at 10 o'clock - 25% ROOTS INSIDE LATERAL454.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"494 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish495.9 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish495.9 ft. AMH - Downstream Manhole, Survey Ends - 32 1172495.9 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK495.9 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
495.9SAV
495.9AMH32 1172
0AMH32 1173
495.9MGOLATERAL AT MH 9 OCLOCK
255.9TFC
93.9TFC
2.2SAV
97.5TFC
332.7TFC
0MWM
397.9TFC
454.9TF
418.3TF
191.6TF
2.2MGOMAG COAT
494SSS
0MWL
418.3RFL25% ROOTS INSIDE LATERAL
495.9MGOLATERAL AT MH 3 OCLOCK
328.9TFC
2SSS

Properties (4)

additional_info
SC345939
custom_field_two
3
customer
LACSD
datetime
2017-09-19T02:05:11-07:00