Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2016, 10:40 AM
  • 19 0144_19 0143_20160314_045259.mp4

Date
03/14/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15334
Time
3:40 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3223
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
03
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0143
Downstream MH
19 0144
Dir. of Survey
Upstream
Length Surveyed
330.1 ft.
Total Length
330.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 19 0143 to 19 0144
MH: 19 0143MH: 19 0144upstream0 ft. AMH - Upstream Manhole, Survey Ends - 19 01443.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish19 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"21.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"121 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"123.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"223.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"225.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"319.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"321.7 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES321.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"325.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start330.1 ft. MWL - Water Level, 10 %of cross sectional area330.1 ft. MWM - Water Mark, 15 %of cross sectional area330.1 ft. AMH - Downstream Manhole, Survey Begins - 19 0143330.1 ft. VC - Vermin Cockroach

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    8.4 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
8.4DAE
308.6TFC
209.1TFC
0MWL
311.1TFC
0MWM
326.3DAGS
4.2DAGS
206.6TFC
330.1AMH19 0144
106.5TFC
104.2TFC
10.6TFC
0AMH19 0143
0VC
8.2TFC

Properties (5)

additional_info
SC305313
custom_field_two
4
customer
LACSD
datetime
2016-03-14T03:40:00-07:00
sewer_category
GRAVITY