Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2016, 05:00 AM
  • 19 0147_19 0146_20160314_221803.mp4

Date
03/14/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15337
Time
10:00 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3224
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
CERRITOS, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
03
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0147
Downstream MH
19 0146
Dir. of Survey
Downstream
Length Surveyed
346.3 ft.
Total Length
346.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 19 0147 to 19 0146
MH: 19 0147MH: 19 0146downstream0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 01470 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES7.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start93.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"96.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"194 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4" - W/ DEPOSITS196.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"244.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"289.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"291.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"328.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 12 o'clock, , within 8 inches of joint: YES338.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES343 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish346.3 ft. AMH - Downstream Manhole, Survey Ends - 19 0146

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock,  , within 8 inches of joint: YES

    0 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 03 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    244.5 ft. - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"

Observations (18)

DistanceCodeObservation
343DAGS
338.7DAE
244.5TBA
93.4TFC
0MGOLATERAL AT MH 3 OCLOCK
328.6DAE
0MWL
194TFW/ DEPOSITS
289.3TFC
7.1DAGS
96.1TFC
291.9TFC
0AMH19 0147
0MWM
346.3AMH19 0146
0MGOLATERAL AT MH 9 OCLOCK
0DAGS
196.4TFC

Properties (5)

additional_info
SC305315
custom_field_two
4
customer
LACSD
datetime
2016-03-14T22:00:40-07:00
sewer_category
GRAVITY