Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2016, 09:42 AM
  • 19 0088_19 0087_20160317_025822.mp4

Date
03/17/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15280
Time
2:42 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
03/17/16
Pre-Cleaning
Not Known
Media Label
K3227
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
LAKEWOOD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0088
Downstream MH
19 0087
Dir. of Survey
Downstream
Length Surveyed
262.7 ft.
Total Length
262.7 ft.
Structural Index
1
Structural Quick
1100
Structural Rating
1
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 19 0088 to 19 0087
MH: 19 0088MH: 19 0087downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 00882.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start49.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"80 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"123.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"127.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"136.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"161.4 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"206.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"252.9 ft. CC - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES260.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"262.7 ft. AMH - Downstream Manhole, Survey Ends - 19 0087262.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"

    161.4 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    252.9 ft. - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
252.9CC
136.9TFC
260.4TFC
80TFA
127.6TFA
0MWM
262.7AMH19 0087
206.8TFA
123.5TFA
2.6DAGS
0MWL
0AMH19 0088
262.7DAGS
49.9TFA
161.4TBA

Properties (5)

additional_info
SC305318
custom_field_two
4
customer
LACSD
datetime
2016-03-17T02:42:36-07:00
sewer_category
GRAVITY