Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 07:12 AM
  • 19 0085A_19 0085_20160311_002851.mp4

Date
03/10/2016
W/O
557968
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00722
PipeID
P15278
Time
11:12 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3222
Sewer Name
19 EAST ARTESIA TRUNK, SECTS 1,2,3,&5
City
LAKEWOOD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
07
Purpose
Routine Assessment
Project
WO_557968_TV19021_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0085A
Downstream MH
19 0085
Dir. of Survey
Downstream
Length Surveyed
169.8 ft.
Total Length
169.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2E11
O&M Rating
65
Overall Index
2
Overall Quick
Overall Rating
65
Pipe schematic from manhole 19 0085A to 19 0085
MH: 19 0085AMH: 19 0085downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 19 0085A0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK2.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"6.6 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES, Start11.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"11.9 ft. VC - Vermin Cockroach61.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"65.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"69.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"77.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"114.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"121.1 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"126.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"132.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"166.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES, Finish169.8 ft. AMH - Downstream Manhole, Survey Ends - 19 0085

Observation photos (2)

  • Water Mark, 15 %of cross sectional area

    0 ft. - Water Mark, 15 %of cross sectional area

  • Deposits Attached Grease, 10 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: YES, Start

    6.6 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
69.5TFC
61.2TBA
6.6DAGS
77.1TBA
132.5TBA
0MWM
11.6TF
0AMH19 0085A
65.4TFC
0MWL
126.5TFC
121.1TBA
0MGOLATERAL AT MH 9 OCLOCK
166.7DAGS
114.2TF
169.8AMH19 0085
2.1TF
11.9VC

Properties (5)

additional_info
SC305312
custom_field_two
4
customer
LACSD
datetime
2016-03-10T23:12:58-08:00
sewer_category
GRAVITY