Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 25, 2017, 11:54 AM
  • 05 0715_05 0714_25092017_045501.mpg

Date
09/25/2017
W/O
658045
Weather
Dry
Operator/Surveyor
CORTEZ ESTEBAN
Sewer ID
Z00521
PipeID
P05938
Time
4:54 AM
Certificate
U-209-8148
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4939
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_658045_TV05308_SEP2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0715
Downstream MH
05 0714
Dir. of Survey
Downstream
Length Surveyed
361.5 ft.
Total Length
361.5 ft.
Structural Index
3
Structural Quick
3423
Structural Rating
18
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 05 0715 to 05 0714
MH: 05 0715MH: 05 0714downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07153 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES6.3 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES12.5 ft. CS - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES15.4 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES52.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES130 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES193 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES315.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES361.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0714

Observation photos (8)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    6.3 ft. - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

    12.5 ft. - Crack Spiral, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    15.4 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    52.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    130 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    193 ft. - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock,  , within 8 inches of joint: YES

    315.3 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
130CM
193CM
0MWL
361.5AMH05 0714
12.5CS
0MWM
315.3DAE
0AMH05 0715
52.4CL
6.3CM
15.4CL
3CM

Properties (4)

additional_info
SC345847
custom_field_two
3
customer
LACSD
datetime
2017-09-25T04:54:44-07:00