Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 7, 2017, 11:04 AM
  • E 0036_E 0035_07092017_040507.mp4

Date
09/07/2017
W/O
654302
Weather
Dry
Operator/Surveyor
CORTEZ ESTEBAN
Sewer ID
Z00028
PipeID
P11263
Time
4:04 AM
Certificate
U-209-8148
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4917
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
W COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
18
Purpose
Routine Assessment
Project
WO_654302_TV01123_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0036
Downstream MH
E 0035
Dir. of Survey
Downstream
Length Surveyed
608.1 ft.
Total Length
608.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole E 0036 to E 0035
MH: E 0036MH: E 0035downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 00360 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area1 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start159.8 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish363 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start409.2 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish409.2 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start441.6 ft. DSF - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish602.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish608.1 ft. AMH - Downstream Manhole, Survey Ends - E 0035

Observation photos (4)

  • Deposits Settled Fine,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    1 ft. - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    363 ft. - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Fine,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    409.2 ft. - Deposits Settled Fine, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
441.6DSF
409.2DSF
0AMHE 0036
0MWL
602.3SAV
363DSF
608.1AMHE 0035
0MWM
409.2DSF
159.8DSF
1DSF
1SAV

Properties (4)

additional_info
SC345824
custom_field_two
3
customer
LACSD
datetime
2017-09-07T04:04:55-07:00